Career Probationary Fire Fighter Runs Out of Air and Dies in Commercial Structure Fire—Michigan

FF ShieldDeath in the Line of Duty...A summary of a NIOSH fire fighter fatality investigation

F2013-14 Date Released: April 15, 2016

Executive Summary

On May 8, 2013, a 29-year-old male career probationary fire fighter died after running out of air and being trapped by a roof collapse in a commercial strip mall fire. The fire fighter was one of three fire fighters who had stretched a 1½-inch hoseline from Side A into a commercial strip mall fire. The hose team had stretched deep into the structure under high heat and heavy smoke conditions and was unsuccessful in locating the seat of the fire. The hose team decided to exit the structure. During the exit, the fire fighter became separated from the other two crew members. The incident commander saw the two members of the hose team exit on Side A and called over the radio for the fire fighter. The fire fighter acknowledged the incident commander and gave his location in the rear of the structure. The fire fighter later gave a radio transmission that he was out of air. A rapid intervention team was activated but was unable to locate him before a flashover occurred and the roof collapsed. He was later recovered and pronounced dead on the scene.

Contributing Factors

  • Risk assessment
  • Communications
  • Crew integrity
  • Fire fighter ran out of air in an IDLH atmosphere
  • Staffing and deployment
  • Arson fire in a commercial structure
  • Lack of automatic fire sprinklers

 

Key Recommendations

  • Fire departments should ensure that an initial risk assessment is performed and continuous risk assessment is performed throughout the incident and the strategy and tactics match the conditions encountered.
  • Fire departments should ensure that fire fighters are trained to understand the influence of building design and construction on structural collapse.
  • Fire fighters and officers should ensure critical benchmarks, such as progress or lack of progress, are communicated to the incident commander and that positive communication discipline are used.
  • Emergency fireground conditions should be communicated and acknowledged on the fireground and radio discipline maintained.
  • Fire departments should ensure that crew integrity is maintained during fire suppression operations.
  • Fire departments should ensure adequate staffing and deployment of resources based on the community’s risk assessment.
  • Fire departments should ensure that fire fighters and officers are properly trained in air management.
  • Fire departments should ensure that fire fighters are properly trained in out-of-air SCBA emergencies and SCBA repetitive skills training.
  • Fire departments should ensure fire fighters are properly trained in Mayday procedures and survival techniques.
  • Fire departments should ensure that fire fighters are trained in situational awareness, personal safety, and accountability.
  • Code-setting organizations and municipalities should consider requiring the use of sprinkler systems in commercial structures.

 

Read the full report